Back to Top
WEIDMULLER U REMOTE I/O UR20-4AI-UI-16-1315620000
Description:
- Analog input modules for the u-remote system are available in a variety of resolutions and wiring options.
- There are 12- and 16-bit resolution versions that can record up to four analog sensors with the highest precision of +/-10 V, +/-5 V, 0...10 V, 0...5 V, 2...10 V, 1...5 V, 0...20 mA, or 4...20 mA.
- Sensors with two or three wires can optionally be connected to each plug-in connector.
- Each channel can have its own set of measurement range parameters.
- Every channel also has a status LED of its own.
- Current measurements with 16-bit resolution and maximum precision for eight sensors at once are made possible by a unique interface unit version (0...20 mA or 4...20 mA).
Specifications:
- Depth: 76 mm.
- Height: 120 mm.
- Width: 11.5 mm.
- Mounting dimension height: 128 mm.
- Storage temperature: -40 °C ... +85 °C.
- Operating temperature: -20 °C ... +60 °C.
- Accuracy: 0.1% FSR.
- Conversion time: 1 MS.
- Internal resistance I: 41.2 Ω.
- Internal resistance U: 100 k Ω.
- Number of analogue inputs: 4.
- Resolution: 16 Bit.
- Response time: < 50 MS.
- Sensor connection:
- 2-wire.
3-wire.
3-wire + FE. - Sensor supply:
- Min: 0 mA.
- Nominal: 750 mA.
- Max: 750 mA.
- Type of connection: Push in.
- Wire connection cross section, finely stranded, max: 1.5 mm².
- Wire connection cross section, finely stranded, min: 0.14 mm².
- Wire cross-section, finely stranded, max. (AWG): AWG 16.
- Wire cross-section, finely stranded, min. (AWG): AWG 26.
- Wire cross-section, solid, max: 1.5 mm².
- Wire cross-section, solid, max. (AWG): AWG 16.
- Wire cross-section, solid, min: 0.14 mm².
- Wire cross-section, solid, min. (AWG): AWG 26.
- Voltage supply: 24 V DC +20 %/ -15 % via the system bus.
- Galvanic isolation: 500 V DC between the current paths.
- Interface: u-remote system bus.
- Module type: Analogue input module.
- Parameter data: 14 Byte.
- Process data: 8 Byte.
- Transmission speed of system bus, max: 48 Mbit.
Write Your Own Review